KEYSTROKES FOR SETUP OF QUADRATURE RATE
If the MENU key does not work, see Section 9 “Enabling & Locking Out Menu Items.”
Press
Menu
Press Digit
Select Key
Press Value Select
Key
Basic meter
_totAL Quadrature total _InPut
Input
_quAdr
Quadrature
Extended _rAtE_ Quadrature rate
_00000 Not applicable 0 Set to zero.
_00000 Leading zeros 0 Blank leading zeros.
1 Display leading zeros.
_00000 Scaling Method 1
0 Input scale factor 1 and offset 1
1 Use coordinates of 2 points method
_00000 Scaling Method 2
Make the same as Scaling Method 1
SEtuP
Setup
_00000
Operation of rear connec-
tor inputs 1 & 2.
True = logic 1 (0V or tied
to digital ground).
False = 0 (5V or open).
0 1 = Meter Reset*, 2 = Function Reset*
1 1 = Meter Reset*, 2 = Meter Hold*
2 1 = Meter Reset*, 2 = Peak or Valley Display*
3 1 = Meter Reset*, 2 = External Gate*
4 1 = Function Reset*, 2 = Meter Hold*
5 1 = Valley Only Display**, 2=Peak Only Display**
6 1 = Function Reset*, 2 = External Gate*
7 1 = Meter Hold**, Peak or Valley Display**
8 1 = Reset Total A**, 2 = Reset Total B**
9 1 = Force Alarm1, 2 = Force Alarm2
A 1 = Meter Reset*, 2 = Display Blank*
B 1 = Function Reset*, 2 = Display Blank*
C 1 = Meter Hold*, 2 = Display Blank*
D 1 = Peak or Valley Display**, 2 = Display Blank**
E 1 = Display Blank, 2 = External Gate*
F 1 = Display Item #2, 2 = Display Item #3
With 1 and 2 at 5V or open, Display Item #1.
-------------------------------------------------------------------
* 1 & 2 both at 0V = Meter Reset (can restore
totals).
** 1 & 2 both at 0V for selections 5, 7, 8, D =
Function Reset* (erases all totals).
__0000 Display mode 0 Normal, overload to exponential format
1 Normal, overload to 999999
Normally select 1, required for Preset function. See
dual signal conditioner for other available modes.
__0000 Counter mode 0 Basic counter
1 Extended counter (required for Quadrature Rate)
__0000 Not applicable 0 Set to 0.
ConFiG
Configura-
tion
__0000 Not applicable 0 Set to 0.