10 8. FRONT PANEL SETUP KEYS Meter Front Panel There are four front panel keys, which change function for the Run Mode and Menu Mode, effectively

Strona 3 - 2. TABLE OF CONTENTS

11 KEYS IN MENU MODE Right Arrow Key (MENU). Pressing steps the meter through all menu items that have been enabled and then back to the

Strona 4 - 3. PRODUCT INTRODUCTION

12 9. ENABLING & LOCKING OUT MENU ITEMS For security reasons and ease of meter operation, any and all menu items may be disabled or &

Strona 5 - 5. SAFETY CONSIDERATIONS

13 10. READING COORDINATES OF 2 POINTS SCALING METHOD When the reading coordinates of 2 points scaling method has been selected under SEtuP, the f

Strona 6

14 11. DC VOLTS, AMPS, PROCESS, STRAIN INPUT The DC Volts, Amps, Process and Strain meters utilize the DC signal conditioner board, which needs to

Strona 7 - RS485 INTERFACE - HALF DUPLEX

15 Board Revisions Q and R 1. Letters indicate jumper position. Jumpers are installed on pins adjacent to letters. 2. Use 5 mm (0.2") jumpers

Strona 8 - 7. MECHANICAL ASSEMBLY

16 KEYSTROKES FOR SETUP If the MENU key does not work, see Section 9 “Enabling & Locking Out Menu Items.” Press Menu Select Key Pr

Strona 9

17 Press Menu Select Key Press Digit Select Key Press Value Select Key 000_0 Operation as a rate of change meter. Extended meter only. 0

Strona 10 - 8. FRONT PANEL SETUP KEYS

18 Press Menu Select Key Press Digit Select Key Press Value Select Key Scaling method “Scale and Offset” if selected under SEtuP SCALE

Strona 11

19 Option board dependent menu items ALSEt. ALS34 dEU1H dEU2H dEU1b dEU2b dEU3H DEU4H DEU3b DEU4b Menu items related to alarm setup These w

Strona 12 - Menu Items

2 1. ORDERING GUIDE Configure a model number in this format: L20201DCV1, CBL01 L…….Digital panel meter with screw terminal connectors. Display

Strona 13

20 12. LOAD CELL & MICROVOLT INPUT Notes 1. See Section 19 to select 10V excitation. 2. Jumpers are 2.5 mm (0.1 in). SCALE &

Strona 14

21 KEYSTROKES FOR SETUP If the MENU key does not work, see Section 9 “Enabling & Locking Out Menu Items.” Press Menu Select Key Press

Strona 15

22 Press Menu Select Key Press Digit Select Key Press Value Select Key 000_0 Operation as a rate of change meter. Extended meter only.

Strona 16

23 Press Menu Select Key Press Digit Select Key Press Value Select Key Scaling method “Scale and Offset” if selected under SEtuP SCALE S

Strona 17

24 Option board dependent menu items ALSEt. ALS34 dEU1H dEU2H dEU1b dEU2b dEU3H DEU4H DEU3b DEU4b Menu items related to alarm setup These w

Strona 18

25 13. AC TRUE RMS VOLTS & AMPS INPUT AC voltage or current measurement utilizes the True RMS signal conditioner board which uses prec

Strona 19

26 can be set for direct readout in (milli)volts or (milli)amperes. Decimal point selection does not affect the counts. For example, a 20V input may

Strona 20

27 KEYSTROKES FOR SETUP If the MENU key does not work, see Section 9 “Enabling & Locking Out Menu Items.” Press Menu Select Key P

Strona 21

28 Press Menu Select Key Press Digit Select Key Press Value Select Key 000_0 Operation as a rate of change meter. Extended meter only. 0

Strona 22

29 Press Menu Select Key Press Digit Select Key Press Value Select Key Scaling method “Scale and Offset” if selected under SEtuP SCALE S

Strona 23

3 2. TABLE OF CONTENTS 1. ORDERING GUIDE ...

Strona 24

30 Option board dependent menu items ALSEt. ALS34 dEU1H dEU2H dEU1b dEU2b dEU3H DEU4H DEU3b DEU4b Menu items related to alarm setup These w

Strona 25 - of 0. The decimal point

31 14. THERMOCOUPLE INPUT The thermocouple signal conditioner board used for temperature measurement can be confi-gured via jumpers for 7 thermocou

Strona 26

32 KEYSTROKES FOR SETUP If the MENU key does not work, see Section 9 “Enabling & Locking Out Menu Items.” Press Menu Select Key Pr

Strona 27

33 Press Menu Select Key Press Digit Select Key Press Value Select Key 000_0 0 No used. ConFG Meter Configuration 00 _ _0 Operation of

Strona 28

34 15. RTD & RESISTANCE INPUT The standard RTD and resistance signal conditioner board can be configured via jumpers for four RTD types (DIN

Strona 29

35 RTD & RESISTANCE CONNECTION With the appropriate jumper settings, RTD and resistance measurements allow 2, 3 or 4-wire RTD hookup to

Strona 30

36 KEYSTROKES FOR SETUP If the MENU key does not work, see Section 9 “Enabling & Locking Out Menu Items.” Press Menu Select Key P

Strona 31 - 14. THERMOCOUPLE INPUT

37 Press Menu Select Key Press Digit Select Key Press Value Select Key SEtuP Meter Setup (continued) 00_00 Control inputs 1 & 2 (co

Strona 32 - True = logic 1 (0V or

38 Press Menu Select Key Press Digit Select Key Press Value Select Key FiLtr Filtering (continued) 00000 Input signal filtering. Can be

Strona 33

39 16. DUAL OR QUAD RELAY OUTPUT OPTION An optional relay board may be installed in the meter main board at plug position P2, adjacent to

Strona 34

4 3. PRODUCT INTRODUCTION Our digital panel meters are versatile, cost effective solutions to a wide variety of monitoring and control application

Strona 35

40 KEYSTROKES FOR SETPOINT SETUP If the MENU key does not work, see Section 9 “Enabling & Locking Out Menu Items.” Press Menu Select Key

Strona 36

41 Press Menu Select Key Press Digit Select Key Press Value Select Key 00000 Alarm operates at and above setpoint (active high) or at

Strona 37 - (continued)

42 17. ANALOG OUTPUT OPTION An optional analog board may be installed in the meter at rear panel jack position J4, adjacent to the signal conditi

Strona 38

43 18. SERIAL COMMUNICATION OPTIONS A serial communications board may be connected to the meter main board at plug position P13 (middle position)

Strona 39

44 Basic Ethernet Board No jumpers needed. RS232 Board e - Normal operation. f - Slave display to RS232 from another meter. g - Pull-up re

Strona 40

45 SERIAL CONNECTION EXAMPLES

Strona 41

46 KEYSTROKES FOR SETUP If the MENU key does not work, see Section 9 “Enabling & Locking Out Menu Items.” Press Menu Select Key P

Strona 42 - 17. ANALOG OUTPUT OPTION

47 Press Menu Select Key Press Digit Select Key Press Value Select Key _0000U Line feed 0 No line feed after carriage return 1 Line feed

Strona 43

48 19. EXCITATION OUTPUT & POWER SUPPLY Three isolated transducer excitation output levels are available from the power supply board. These ar

Strona 44

49 20. INSTRUMENT SETUP VIA PC Instrument Setup software is a PC program which is much easier to learn than front panel programming. It is of

Strona 45 - SERIAL CONNECTION EXAMPLES

5 4. RECEIVING & UNPACKING Your meter was carefully tested and inspected prior to shipment. Should the meter be damaged in shipm

Strona 46

50 SETUP OF CONNECTED METER A setup file can be retrieved from the meter (DPM => Get Setup), be edited (View => Setup), be s

Strona 47

51 • The Readings pull-down menu provides three formats to display DPM data on the PC monitor. Use the Pause and Continue buttons to co

Strona 48

52 21. CUSTOM CURVE LINEARIZATION Curve.exe is a DOS-based, executable PC program used to set up an Extended meter so that the readings have a

Strona 49

53 4) Equation entry mode, where the coefficients of a polynomial Y = K1X^P1 + K2X^P2 + K3*X^P3 + … are entered. Up to 20 terms are allowed. An offs

Strona 50 - The Commands pull-down menu

54 22. METER CALIBRATION All analog input and analog output ranges of the meter have been digitally calibrated at the factory p

Strona 51

55 23. SPECIFICATIONS Meter Display Type ...5 LED, 7-segment, 14.2mm (.56") high digits & 3 LED indic

Strona 52

56 DC Volts Range Resol. Resist. Error 200.00 mV 2.0000 V 20.000 V 200.00 V 300.0 V 10 µV 100 µV 1 mV 10 mV 100 mV 1 GΩ 1 GΩ 10 MΩ 10 MΩ 10 MΩ 0.

Strona 53

57 Load Cell Input Range Resolution Resistance Zero Range Span Range Error 20.000 mV 50.000 mV 100.00 mV 250.00 mV 500.00 mV 1 µV 2.5 µV 5 µV 1

Strona 54 - 22. METER CALIBRATION

- 58 - Accuracy ...Meter input accuracy ±0.02% of full scale analog output Resolution ...

Strona 55 - 23. SPECIFICATIONS

- 59 - 24. GLOSSARY OF TERMS Adaptive Filter Threshold A threshold which causes an adaptive moving average filter to be reset to the latest readi

Strona 56

6 6. CONNECTOR WIRING INFORMATION CONNECTORS Connectors for signal and power are UL-rated screw-clamp terminal blocks that plug into mating jacks o

Strona 57

- 60 - Deviation limits are programmed by entering menu item dEU1b for Alarm 1 and dEU2b for Alarm 2. The deviation band equals two limits.

Strona 58 - Environmental

- 61 - Menu Mode The meter programming mode used for input and range selection, meter setup, and meter configuration. Entered into from the R

Strona 59 - 24. GLOSSARY OF TERMS

- 62 - Remote Display A display mode which allows the meter to serve as a remote display to another meter when connected to it by a 4-wire phone

Strona 60

- 63 - Scaling, Reading Coordinates of 2 Points Method A scaling method, where the low and high input values are determined from actual

Strona 61 - Peak Display

- 64 - 25. WARRANTY Laurel Electronics Inc. warrants its products against defects in materials or workmanship for a period of one year from the d

Strona 62

7 P3 - SERIAL COMMUNICATIONS P4 - ANALOG OUTPUT N/CISO GNDRXTXRTSN/CGNDTXRXRTSRS232 INTERFACE Computer654321ISO GNDBRXARXATXBTXISO GND

Strona 63

8 7. MECHANICAL ASSEMBLY REMOVING THE REAR PANEL First remove any connectors. Use one hand to press in the two sides of the rear of

Strona 64 - EXCLUSIVE REMEDIES

9 Note: Corresponding main board and option board connectors have the same number of electrical lines. When an option board is correctly